Electronic Theses and Dissertation
Universitas Syiah Kuala
PENGGUNAAN AVR (AUTOMATIC VOLTAGE REGULATOR) UNTUK MENGATUR TEGANGAN PADA SALURAN UDARA TEGANGAN MENENGAH YANG DISALURKAN DARI GI MEULABOH KE EXPRESS CALANG DI PT.PLN (PERSERO) UNIT LAYANAN PELANGGAN TEUNOM
Pengarang
Vivin Qoriani. S - Personal Name;
Dosen Pembimbing
Nomor Pokok Mahasiswa
1804005010002
Fakultas & Prodi
Fakultas Teknik / Teknik Listrik (D3) / PDDIKTI : 20403
Subject
Kata Kunci
Penerbit
Banda Aceh : Universitas Syiah Kuala., 2021
Bahasa
Indonesia
No Classification
-
Literature Searching Service
Hard copy atau foto copy dari buku ini dapat diberikan dengan syarat ketentuan berlaku, jika berminat, silahkan hubungi via telegram (Chat Services LSS)
INTISARI
PENGGUNAAN AVR (AUTOMATIC VOLTAGE REGULATOR) UNTUK MENGATUR TEGANGAN PADA SALURAN UDARA TEGANGAN MENENGAH YANG DISALURKAN DARI GI MEULABOH KE EXPRESS CALANG DI PT.PLN (PERSERO) UNIT LAYANAN PELANGGAN TEUNOM
Oleh
Vivin Qoriani . S
1804005010002
PT.PLN (Persero) merupakan Badan Usaha Milik Negara (BUMN) yang bergerak di bidang penyediaan energi listrik. Umumnya distribusi energi listrik dimulai dari penyulang yang keluar dari GI (Gardu Induk) kemudian disalurkan pada APJ (Area Pelayanan Jaringan) dengan besar tegangan 20 kV yang sering disebut dengan Jaringan Tegangan Menengah (JTM), kemudian di salurkan ke rayon-rayon (ULP). Jaringan Tegangan Menengah menyalurkan listrik dengan jarak yang cukup jauh yang menyebabkan adanya jatuh tegangan dan rugi-rugi daya. Upaya perbaikan jatuh tegangan dilakukan dengan pemasangan AVR ( Automatic Voltage Regulator ). Penelitian ini menghitung jatuh tegangan dan rugi-rugi daya pada penyulang expres Calang PT PLN (Persero) Rayon Teunom dari GI Meaulaboh ke Expres Calang dengan panjang jaringan 91 kms . Total jatuh tegangan untuk penyulang dari GI Meulaboh ke Expres Calang adalah 3,96 kV, dihitung saat beban puncak. Dan presentase total jatuh tegangan sebesar 11,9 % ini masih dalam standar PLN karena belum melebihi standar yang telah ditetapkan yaitu -10% dari tegangan nominalnya. Jatuh tegangan sangat dipengaruhi oleh Panjang penghantar, untuk mengatasi drop tegangan penyulang Expres Calang , maka dilakukan pemasangan AVR , dengan dilakukan Pemasangan AVR (Automatic Voltage Regulator) tegangan terima mengalami peningkatan sebesar 20,128 kV yang sebelumnya sebesar 18,5 kV , dengan hitungan rasio yang didapat sebesar 0,857. Dan rugi – rugi total tanpa pemasangan AVR untuk penyulang Expres Calang sebesar 888, 42 kW , dengan pemasangan AVR (Automatic Voltage Regulator) sebesar 1.108,59 kW . Sehingga semakin sering penggunaan AVR untuk menaikkan tegangan maka rugi-rugi akan semakin besar .
Kata kunci : Jatuh tegangan , Automatic Voltage Regulator, Rugi-rugi tegangan .
ABSTRAK
USING AVR (AUTOMATIC VOLTAGE REGULATOR) TO CONTROL THE VOLTAGE ON THE MEDIUM VOLTAGE AIR LINE DELIVERED FROM MEULABOH GI TO EXPRESS CALANG AT PT.PLN (PERSERO) TEUNOM CUSTOMER SERVICE UNIT
Oleh
Vivin Qoriani . S
1804005010002
PT. PLN (Persero) is a State-Owned Enterprise (BUMN) which is engaged in the provision of electrical energy. Generally, the distribution of electrical energy starts from the feeder coming out of the GI (Substation) then distributed to the APJ (Network Service Area) with a voltage of 20 kV which is often referred to as the Medium Voltage Network (JTM), then distributed to the rayons (ULP). . Medium Voltage Networks distribute electricity over long distances which cause voltage drops and power losses. Efforts to improve the voltage drop are carried out by installing AVR (Automatic Voltage Regulator). This study calculates the voltage drop and power losses on the PT PLN (Persero) Rayon Teunom Express Calang feeder from GI Meaulaboh to Expres Calang with a network length of 91 kms. The total voltage drop for the feeder from GI Meulaboh to Expres Calang is 3.96 kV, calculated at peak load. And the percentage of the total voltage drop of 11.9% is still within the PLN standard because it has not exceeded the predetermined standard, which is -10% of the nominal voltage. The voltage drop is strongly influenced by the length of the conductor, to overcome the voltage drop of the Calang Express feeder, then the AVR is installed, by installing the AVR (Automatic Voltage Regulator) the receiving voltage has increased by 20.128 kV which was previously 18.5 kV, with the calculated ratio obtained of 0.857. And the total losses without the installation of AVR for the Calang Express feeder are 888.42 kW, with the installation of AVR (Automatic Voltage Regulator) of 1,108.59 kW. So the more often the use of the AVR to increase the voltage, the losses will be even greater.
Keywords : Voltage drop, Automatic Voltage Regulator, Voltage loss
.
Tidak Tersedia Deskripsi
STUDI KINERJA STEP VOLTAGE REGULATOR TERHADAP PERBAIKAN TEGANGAN PADA SISTEM DISTRIBUSI 20 KV DI PT.PLN (PERSERO) GARDU INDUK BANDA ACEH (Rahmad, 2014)
OPTIMASI PENEMPATAN KAPASITOR PADA SALURAN DISTRIBUSI 20 KV TEUNOM LAMNO PT PLN PERSERP AREA MEULABOH DENGAN METODE KOMBINASI FIREFLY FORWARD-BACKWARD SWEEP (Zakwansyah, 2019)
DESAIN RANGKAIAN KENDALI PENGISIAN DAN PEMAKAIAN ENERGI BATERAI PADA PEMBANGKIT LISTRIK TENAGA BAYU (PLTB) BERBASIS MIKROKONTROLER ATMEGA32 (Saniman R, 2014)
PERANCANGAN SEPATU PENGISI DAYA SEBAGAI APLIKASI PENGISI DAYA PADA GADGET (Isnaini Sukandar, 2016)
PERANCANGAN INSTALASI LISTRIK SALURAN KAWAT UDARA TEGANGAN RENDAH (SKUTR) DI KOMPLEK PERUMAHAN PANGGOI INDAH LHOKSEUMAWE (Defri Saputra, 2014)